Wall Mounted Fan Coil FCU For Data Centres Free Cooling System
Features:
1. The maximum air flow of at least 2000 m3 / h.
2. Minimum airflow is not more than 700 m3 / h.
3. Power supply 36-56 VDC (direct current).
4. Power consumption at the maximum air flow isn’t more than 300 W.
5. Power consumption at a minimum flow of air isn’t more than 20 W.
6. The power of the electric heater at least 1.5 kW, voltage 220V /
50Hz.
Technical Data:
Structure:
FCU should has:
1. Insulated body and the valve free cooling for inadmissibility
through freezing at outdoor temperatures down to - 40 ° C by the
cold climate zone, and up to - 20C in the performance for the warm
climate zone;
2. Free cooling valve actuator with analog control, which allows
smoothly change the position of the valve;
3. Air filter cassette-type, folding to replace the filter element,
contamination control system;
4. Mosquito protection (pre-filter);
5. The prevention of access of outside air, controlled by a signal
fire system;
6. Control system aerodynamic resistance cleaning filter (air flow
pressure sensors at the inlet and outlet filters);
7. Electric heater, controlled by the controller (as an option).
8. FCU should has double filter which can protect BS from dust
Application:
Data centres or IT environments in colder climates.
![]() |