Package Type Hygienic Air Handling Units Horizontal Chilled Water Type

Categories Clean Room Air Conditioning System
Brand Name: Shenglin
Model Number: SL-ZKW Series
Certification: CE
Place of Origin: China
MOQ: 1
Price: 4999~30000USD/unit
Payment Terms: T/T, Western Union
Supply Ability: 100 Units Per Month
Delivery Time: 35~40days
Packaging Details: Plywood wooden box or pallet
Type: Chilled water type
Air cooled or water cooled: Air cooled
Heater type: Steam or water coil
Structure type: Cabinet/ ceiling / vertical / horizontal type
Fan type: Direct drive motor or belt-driven
Application: hotels, theaters, shopping malls, office buildings
Air volume: 3000~50000m³/h
Optional installation accessories: Air valve, air duct or air grill
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Package Type Hygienic Air Handling Units Horizontal Chilled Water Type

Package Type Hygienic Air Handling Units Horizontal Chilled Water Type
Feature:
1, Complying with above China Standard, which is from ARI standard. ISO9001 and ISO14001 qualified.
2, Choose best materials, main components are from China top brand or imported.
3, The modular casing design, easy interchanging each other. easy install,easy transport,easy maintaince.
4, Unique no-cold-bridge design, improve the insulation and air tightness, total air leak rate ≤2.5%;
5, With dynamic balanced double inlet Centrifugal fan, with good air dynamic features, and accurate working, high efficiency, low vibration, low noise etc.
6, High efficient heat exchanger coil, ensure to provide the enough cooling capacity to the unit. And also high efficient breakwater panel is provided if required, water flow in coil ≤3×10-4kg/kg
7, Strong structure, good looking and permanent color.
8, Reasonable inside structure, with the suitable space for maintenance and cleaning.
9, Casing sheet: Provide double-skin construction constructing Sandwich type comprising 0.5mm thick galvanized internal and external skins and with 30mm thick polystyrene insulation of minimum 45kg/m3 density. Good airproof material is use between the casing and the frame to reduce the rate of the air leak.
Technical Data:
Chilled Water Air Handing Unit Spec. Table No. 1
Model SL-ZKW-20406080100150200250300
Air volume(m³/h)20004000600080001000015000200002500030000
Outlet air pressure(pa)300300400500500600750750750
Supply fan capacity(kw)1.11.52.245.511151518.5
Cooling4 RowsReturn air(kw)12.223.935.9486090120150179
water flow(m³/h)2.24.26.18.210.515.320.423.828.2
all fresh air(kw)2243.86290112156210265310
water flow(m³/h)3.87.71115.519.227.336.545.855
pipe diameter (DN)253240404050656580
6 RowsReturn air(kw)1730.145.26075113151188210
water flow(m³/h)2.85.37.710.513.619.225.530.236
all fresh air(kw)30.55888118150200288355420
water flow(m³/h)5.11015.220.226.235.5497072.5
pipe diameter (DN)323240405065658080
8 RowsReturn air(kw)18.335.2537090132176220264
water flow(m³/h)3.26.28.912.216.222.230.237.244.2
all fresh air(kw)34.870101138178245332410500
water flow(m³/h)5.81217.523.530.842.557.17185
pipe diameter (DN)323240405065658080
Heating2 RowsReturn air(kw)20426084108150200250300
water flow(m³/h)0.81.92.63.74.66.58.71113
all fresh air(kw)18385470100125180210280
water flow(m³/h)0.81.72.43.24.55.57.81012
pipe diameter (DN)253240404040505065
4 RowsReturn air(kw)285680110140200250320380
water flow(m³/h)1.22.43.54.86.391113.518.2
all fresh air(kw)326290125150220300380450
water flow(m³/h)1.52.73.85.46.89.513.516.219.5
pipe diameter (DN)323240404050506565
Function section
outside dimension
Mixing sectionLength(mm)500500500550600800800800800
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Pre-filter sectionLength(mm)100100100100100100100100100
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Medium efficiency filter sectionLength(mm)500500500500500500500500500
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Cooling coil sectionLength(mm)60060070070070080080010001000
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Heating sectionLength(mm)300300300400400400400400400
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Humidifying sectionLength(mm)400400400400400400400400400
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Fan sectionLength(mm)50050090040011001400160017001850
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Current balance sectionLength(mm)400400500900500600600600700
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Sound deadening sectionLength(mm)800800800500800100010001000100
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
Air outlet sectionLength(mm)400400400800500600600800800
Width(mm)9509501080125016001600200022002200
Height(mm)9809801080125013201470168018802200
1. Cooling condition: supply and return water temp7/12℃,
indoor dry bulb/ wet bulb temp35/28℃, fresh air dry bulb/ wet bulb temp35/28℃

2. Heating condition conditions: supply and return water temp60/50℃,
indoor dry bulb/ wet bulb temp20/ -℃, fresh air dry bulb/ wet bulb temp7/6℃

3. The air volume, residual pressure and power in the table are standard parameters,
and are able to be customized

4. Heater, humidifier and heat recovery device are optional, which can be configured as spacific form according to customer's requirements

5. G4 filter is adopted as the unit standard, which can be configured as other form according to customer's requirements

6. The length and size are determined by the functional sections. Please consult us for details.


Application:

The units are widely used in the air system of many inductries like mechanical ,electronic, textile,medical,chemical,energy and foo inductries ,etc. the units are also ideal solution for restaurants, office buildings,hospitals,theaters,supermarkets and palaestra.